Engineering

Voltage Drop Calculator

Every foot of wire adds resistance, and resistance eats voltage before it reaches your load. Pick the wire gauge, enter the one-way run length, the load current and your source voltage — the calculator returns the drop in volts and percent, and whether you are inside the 3% rule of thumb.

Result
—
Voltage drop (%)
—
Drop (volts)
—
Voltage at load
—
Verdict
—

How the voltage drop calculation works

Current flowing through wire resistance loses voltage in proportion:

VD = 2 × L × I × R ÷ 1000

The factor of 2 accounts for the round trip — current travels out on the hot conductor and back on the neutral, and both contribute drop. L is the one-way run in feet, I the load current, and R the conductor resistance in ohms per 1000 ft (the calculator uses standard copper values at operating temperature; aluminium runs roughly 1.6× higher resistance for the same gauge). Drop as a percentage is simply VD ÷ source voltage.

Worked example

A 15 A load at the end of 100 ft of 12 AWG on a 120 V circuit: VD = 2 × 100 × 15 × 1.59 ÷ 1000 = 4.77 V, which is 3.97% of 120 V — slightly over the classic 3% branch-circuit recommendation, and the load sees about 115.2 V. Stepping up to 10 AWG cuts the drop to 2.50%. This is exactly why long runs to sheds, well pumps and RV hookups deserve a wire-size upgrade even when ampacity tables say the small wire "is fine".

The 3% and 5% guidelines

Common practice (reflected in NEC informational notes and the wiring of every reputable electrician): keep branch-circuit drop ≤ 3% and total drop from the service to the load ≤ 5%. Sensitive electronics and motors care — a motor fed 10% low draws more current, runs hotter and loses torque roughly with the voltage square.

Frequently asked questions

1. What is an acceptable voltage drop?

Common guidelines: no more than 3% on a branch circuit and 5% total from the service entrance to the load. Sensitive equipment and long motor runs benefit from staying well under those figures.

2. Why is the length doubled in the formula?

Current must travel to the load and back, so both the hot and neutral conductors contribute resistance. The formula uses one-way length multiplied by two.

3. How much better is 10 AWG than 12 AWG?

10 AWG copper has about 1.00 Ω per 1000 ft versus 1.59 for 12 AWG — roughly 37% less drop for the same run and load. Doubling circular-mil area halves resistance.

4. Does voltage drop waste energy?

Yes — the lost watts heat the wire for nothing. A 4.8 V drop at 15 A dissipates about 71 W of pure loss, which is why oversized conductors often pay for themselves on long, heavily loaded runs.

Related tools